S-3, r. 2 - Regulation respecting safety in public buildings

Full text
11.1. Number of exits in family-type buildings:
The floor area of a family-type building shall be served by at least 2 exits.
Notwithstanding the foregoing, a floor area that is no more than 1 storey above or below the ground floor may be served by only 1 exit where:
(a)  the area does not exceed 150 m2;
(b)  the maximum distance to the exit door does not exceed 15 m;
(c)  no bedroom door giving onto a public corridor, in a hotel, is located more than 6 m from an indoor stairway used as an exit for that bedroom, except where the latter has another means of egress.
For the purposes of the second paragraph, an inside stairway that does not have a fire separation and leads to no more than 2 m from an outside door exit is considered to be an exit, except in the case of a day care centre.
O.C. 466-95, s. 4.